Power • 220-240 V~ 50/60 Hz • Single input feed • 16 A maximum input current • Lightning strike protection meets ANSI/IEEE standard C62.41 and IEC 61000-4-5. Can withstand voltage surges up to 6000 V~ and current surges up to 3000 A. • ESD-protection exceeds agency requirements per IEC-61000-4-2 • For ungrounded delta feed applications, contact Lutron. Regulatory Approvals • Complies with IEC/EN 60669 • Lutron Quality Systems registered to ISO 9001.2015 • CE marked Environment • For thermal specifications, see Mounting section • Relative humidity: less than 90% non-condensing • For indoor use only Output Zone Ratings • Each zone is rated at 5 A for switching. Rated for resistive, inductive, or capacitive lighting loads as defined by IEC/EN 60669. • Air gap off per output. • No minimum load per output. • Outputs cannot be used to control general purpose receptacles.